Item | Electrical characteristics |
IpN/Primary nominal current | 1500A |
IpM /Primary current measuring range | ±4500A |
ISN/Output current | 4V |
Vc/Supply voltage | ±15×(1±5%)V |
δi/Accuracy(excluding offset) | ≤±1%(0~IPN @25℃) ≤±4%(IPN~IPM @25℃) |
δz/Electrical offset | ≤±20mV(@25℃,1×IPN) |
δi/Linearity error | ≤1%(0~IPN@25℃) ≤4%(IPN~IPM @25℃) |
δZT/Temperature coeficient of ǒa | ≤±1mVʃC(-40℃~+85℃) |
Tr /Step response time to 90 %of len | ≤5us |
Ic/Curent consumption | ≤25mA+VSN/RM |
BW(-3dB)BW/Frequency bandwidth | DC…25kHz |
RM/Load resistance | ≥2kΩ |
Ris/Isolation resistance | ≥1000 MΩ(@2500V) |
Ud/Voltage for AC insulation test | 5kVrms/50Hz/1min |